3
Operation
3.2
Turning Off the Unit
The emergency shutdown procedure is on the inside rear cover.
Procedure:
1
One at time, turn off the loads.
2
Switch off the Battery circuit breaker.
3
Switch off the Input circuit breaker.
4
If servicing the unit, switch off the utility circuit breaker supplying the unit.
DANGER: During servicing put a warning note on the circuit breaker supplying the unit.
Shutdown Finished
Figure 3.2
Turning the Unit Off
3
2
2
3