Testing the battery backup time, 1 testing the battery run time, How to measure the battery back up time (sec – Alpha Technologies CFR 3000, CFR 3000RM User Manual

Page 65: Tion 5.1), 1 testing the battery backup time

Advertising
background image

59

5

Maintenance

5.1

Testing the Battery Backup Time

This test measures how long the batteries can provide backup power by having them power the
loads until they are discharged.

Tips:

This test should be done once a year when the batteries are new. When the batteries are

three years old or older, it should be done once every six months.

This test should be done when new loads are connected to the unit.

The unit should have been in Line Present mode for 24 hours before starting this test so

the batteries are fully charged.

Do a self test (Section 3.3) first. If it passes then do this test. If it doesn’t find out why

before proceeding.

For reference, compare your measured time to the times listed in Section 5.6, “Battery

Run Times.” Because of various factors, your time may not match the times listed.

Procedure:

1

Switch off the Input circuit breaker.

The display panel’s Line Failure LED turns on showing the unit is
operating on backup battery power.

Record this start time.

2

The Low Battery Warning LED turns on.

Record this time.

3

The run time is the time between

1

and

2

.

4

Switch on the Input circuit breaker.

The unit runs on line power and starts charging the batteries.

Battery Backup Time Test Finished