2.3 Cordex System Controller

A Cordex system controller (CXCP), mounted in one of the BDFBs, provides easy access to controls and display

status. The CXCP provides comprehensive setup, control, monitoring and communication for Alpha DC power

systems.
The CXCP features include the following:
• Local and remote communications
• User definable alarms
• Daily logging of events and system statistics
See the CXC Software Manual shipped with your order for detailed information.

Figure 6 — CXCP controller mounted in a distribution BDFB

Progress and status indication

The LED lights are also used in the following situations:
• Base unit validation—all three LEDs illuminate
• File transfer—red LED illuminates

2.3.1 Front Panel Reset Button

If it is necessary to reset the controller (before a power-down for example), use the LCD to select the reset menu

item. Resetting from the LCD initiates a soft reset with no loss of data.
The reset button (Figure 6) on the front panel initiates a hard reset of the CXC microprocessor. No data is saved

and should be used only If the controller is hung up. It takes approximately 15 seconds before the display reap-

pears after pressing the reset button.

System status LEDs

LCD
screen

Craft port

Reset button

2.3.2 Front Panel LEDs

Three LEDs are located on the front panel: one green, one yellow, and one red. These LEDs display the alarm

status of the system, controller progress and status during startup, as well as file transfers.

Alarm conditions

Only one LED light is illuminated at a time during alarm

conditions. Each LED light corresponds to a specific

alarm. A built-in audio speaker sounds an intermittent

tone during active alarms.

Illuminated LED

Alarm

Green

OK, no alarms

Yellow

Minor alarm, no major alarms

Red

Major alarm