3 dc input, Figure 12 — dc input bus bars – Alpha Technologies CXDS-M 600_600-19 User Manual

Page 24

Advertising
background image

9400002-J0 Rev A

22

5.3 DC Input

• Single feed, 600A max
• Dual feed 1200A max

5.3.1 DC Cables from the DC Plant Source

Input cables should be sized for a 0.25 V drop from power system to the CXDS-M at full load including anticipat-

ed growth. The cables should also meet ampacity requirements of the protective device.

DC

Plant Cables

Connect the DC plant return cables to the return bus bars (shown in Figure 12). The return bus bars are designed

for a connection of 3/8" holes on 1" centers.

Live DC Plant Cables

Connect directly to the live bus bar. Protect input feeds with a high capacity fuse or circuit breaker.

Figure 12 — DC input bus bars

Feed A

Feed B

Return