0 installation, 1 alpha xm series 2 and edsm card (hms-enabled) – Alpha Technologies XP-EDH4 - Technical Manual User Manual

Page 15

Advertising
background image

15

745-419-B0-001 Rev. A (11/2013)

2.1 Alpha XM Series 2 and EDSM Card (HMS-Enabled)

The EDH4 transponder can be interfaced to power supplies that support the SCTE-HMS interface. In

addition, the EDH4 transponder can receive battery string data through the HMS interface port and can

measure battery strings directly. If battery data is present from both the HMS interface and the direct

battery connection (EDH4 BAT A/B or BAT C/D), the EDH4 transponder uses the direct battery connection

data.

2.0 Installation

When installing the EDH4 transponder (which is recognizable by the presence of 6 LEDs on the

front panel, as opposed to 4 on the older models), care must be taken to recognize the difference

between the new labeling of the 4 pin front panel connector “CNTL.” This is to be used with

a battery mat heater control. The older units had an identical connector, labeled “AUX PWR.”

DAMAGE WILL RESULT if the older cable is plugged into the new transponder.

CAUTION!

EDH2

EDH3

EDH4

CNTL

AUX PWR

AUX PWR

Fig. 2-1, Identifying the CNTL Connector

Alpha’s Enhanced Digital Status Module (EDSM) is a status monitoring interface for the XM Series

2 power supply. The EDSM continuously gathers power supply, generator, and battery data. Data is

transferred to an industry standard digital transponder (DT) using a serial interface, specified by the ANSI/

SCTE25-3 standard. DT connector equipped EDSMs connect to either an embedded digital transponder

or an external digital transponder such as the EDH4.

Required Materials

RF Cable

Customer supplied

HMS-022 Interface Cable

Alpha p/n 875-734-19

Battery Sense Wire Harness

36V single string, 6', Alpha p/n 874-842-21
36V single string, 9', Alpha p/n 874-842-27
36V dual string, 9', Alpha p/n 874-842-28
48V single string, 9', Alpha p/n 874-841-25
48V dual string, 9', Alpha p/n 874-841-24

Battery Heater Mat Control Cable (optional)

Alpha p/n 875-627-20

Ethernet Cable (optional)

Alpha p/n 875-734-19

EDSM Interface Card with DT Connector

Configurable (contact Alpha Technologies

for order information)

Surge Protector with Ground Block

Alpha p/n 162-028-10

Tamper Wire Harness

Enclosure-specific (enclosure option)

In Line Lightning Arrestor w/pass thru (130V) L-G, L-N, N-G

Alpha p/n 162-046-10 (not compatible with

240V circuits/receptacles)

Advertising