The batteries in each string are numbered sequentially from 1 through 2 (in the case of 24 volt

strings), from 1 through 3 (in the case of 36 volt strings), and from 1 through 4 (in the case of

48 volt strings) where Battery 1 of any string type is the designator of the first battery when

referenced from battery common or the negative end of the string.
The transponder reports the voltage of each monitored/measured battery with a resolution of 0.1

VDC with a maximum measurement accuracy tolerance of ±2% from the nominal 12V battery

measurement.

Table 3-11, Battery Connector Pinouts

PIN NAME

DEFINITION

1

COMMON

MOST NEGATIVE TERMINAL OF BOTH BATTERY STRINGS

2

BATT 1 POS. A/C 12 V STRINGS

POSITIVE TERMINAL OF BATTERY 1 IN THE A OR C STRING

3

BATT 2 POS. A/C 24 V STRINGS

POSITIVE TERMINAL OF BATTERY 2 IN THE A OR C STRING

4

BATT 3 POS. A/C 36 V STRINGS

POSITIVE TERMINAL OF BATTERY 3 IN THE A OR C STRING

5

BATT 1 POS. B/D 12 V STRINGS

POSITIVE TERMINAL OF BATTERY 1 IN THE B OR D STRING

6

BATT 2 POS. B/D 24 V STRINGS

POSITIVE TERMINAL OF BATTERY 2 IN THE B OR D STRING

7

BATT 3 POS. B/D 36 V STRINGS

POSITIVE TERMINAL OF BATTERY 3 IN THE B OR D STRING

8

BATT 4 POS. A/B OR C/D 48V STRINGS POSITIVE TERMINAL OF BATTERY 4 IN THE A/B OR C/D STRING

3.0

Configuration and Operation, continued

3.10 Transponder Cabling

3.10.1 Battery Cable

Cable Pinout Details

Refer to the illustration at the end of this chapter to see the connector locations on the EDH4

transponder.

Each battery connector can connect/monitor up to two series of battery strings, typically in 24,

36, or 48 Volt configurations, for a maximum of four strings per transponder. Following is the pin

number configuration chart.

The maximum voltage tolerable without damage to the transponder on any pin of the battery interface

connectors is 64 Vdc.

NOTE: