17.

Setting the electronic position transmitter RWG (option)

— For remote indication or external control —

After mounting the actuator on the valve, check setting and adjust, if necessary
(refer to subclauses 17.1 or 17.2).

The position transmitter board (figure W) is located under the cover plate
(figure Y).

30

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Operation instructions

Terminal plans

KMS TP_ _ 4 / _ _ _

3- or 4- wire system

KMS TP _ 4 _ / _ _ _
KMS TP _ 5 _ / _ _ _

2-wire system

Output current

I

a

0 – 20 mA, 4 – 20 mA

4 – 20 mA

Power
supply

U

v

24 V DC, ±15 %

smoothed

14 V DC + (I x R

B

),

max. 30 V

Max. input
current

I

24 mA at 20 mA

output current

20 mA

Max. load

R

B

600

Ω

(Uv - 14 V) / 20 mA

Table 3: Technical data RWG 4020

Figure W: Position transmitter board