Signals 9 – AUMA Electric multi-turn actuators SA 07.1 - 16.1_SAR 07.1 - 16.1 MATIC AM 01.1 - 02.1 User Manual

Page 9

Advertising
background image

4.

Additional information to the wiring diagram legend

Information A:

A running indication is possible if blinker transmitter (S5) is installed
(opening and closing of contacts).
Direction CLOSE:

Connections X

K

6 - X

K

7

Direction OPEN:

Connections X

K

6 - X

K

8

Contacts remain closed in end position.
When connected to an external PLC, the blinking signal can be switched off via
the DIP-switches (table 4, page 35).

Information B:

The type of seating in the end positions is determined by the valve manufac-
turer. The setting is done at the programming switches S1-2 and S3-2
(see page 35). The tripping of a torque switch in an intermediate position
switches off the actuator and causes a fault signal.
The limit switches serve for signalization when switching off by torque seating.
They need to be set so that the appropriate switch is tripped shortly before
reaching the end position. If the torque switch trips before the limit switch, the
actuator is switched off and a fault signal is generated.
For further programming possibilities, e.g. self-retaining in operation mode
REMOTE, see table 4, page 35.

Information D:

The following faults are registered and can be transmitted to the control room as
a potential-free collective fault signal:

- Power failure
- Phase failure
- Motor protection tripped
- Torque switch tripped in mid-travel.

This signal can be switched off on the logic board, see table 4, page 35.

Information E:

Input signals according to DIN 19 240.
The nominal operation current of inputs X

K

2, X

K

3, and X

K

4 amounts to

10 – 15 mA. If the internal voltage 24 V DC is used for remote control, it must
only be connected via potential-free contacts.

Information F:

In case of wrong phase sequence, the running direction is automatically
adjusted. In case of a phase failure, the actuator stops. The fault is indicated at
LED V14 on the interface board (see page 34). For collective fault signal, see
information D.

Information G:

Potential-free contacts are available for signals. The internal control voltage
(X

K

11 / + 24 V and X

K

5 / – 24V) must not be used for external lamps, relays,

etc.

Please note that this information only pertains to point to point
drawings.

9

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1

Operation instructions

with actuator controls AUMA MATIC AM 01.1 / AM 02.1