22.

Timer (option)

The timer board is used to increase the operating time for the entire or any por-
tion of the valve travel.

Example:

In order to avoid water hammer in long pipelines, stepping mode can be chosen
for any part of the travel.

.

The timer is installed in the actuator controls AUMA MATIC instead of the
interface board.

.

Electronic timer is not possible in combination with positioner.

22.1 Functions of the diagnosis LEDs (timer)

V14 is illuminated:

Phase failure and/ or motor protection tripped.
For version with PTC thermistor: reset by
selector switch position

III

at local controls.

V15 is illuminated:

Torque fault: Tripping torque was exceeded before
reaching the end position.

V21 is illuminated:

Stepping mode in direction CLOSE is switched on.

V22 is illuminated:

Stepping mode in direction OPEN is switched on.

49

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1

Operation instructions

with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Figure AL: Cover plate for timer A1.6