20.2 Programming the logic board

The type of seating – limit or torque seating – (switch S1-2 and switch S3-2, fig-
ure AC) must be determined by the valve manufacturer.

.

Set desired programming according to table 4 at the switch S2-2.

35

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1

Operation instructions

with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Position 1:

Limit
seating

in end position OPEN

Position 2:

Torque
seating

in end position OPEN

Position 1:

Limit
seating

in end position CLOSED

Position 2:

Torque
seating

in end position CLOSED

S3-2

S1-2

S2-2

Figure AC: Logic board A2

DIP switch S2-2

Programming

(ON = pressed)

Direction CLOSE

Direction OPEN

Self-retaining REMOTE

Push-to-run operation REMOTE

Self-retaining LOCAL

Push-to-run operation LOCAL

Blinker transmitter (option)

activated

deactivated

Torque fault: Torque switch trip-
ping (in mid-travel) contained in
collective fault signal

included

not included

Table 4