1 functions of the diagnosis leds (timer) – AUMA Electric multi-turn actuators SA 07.1 - 16.1_SAR 07.1 - 16.1 MATIC AM 01.1 - 02.1 User Manual

Page 48

Advertising
background image

Example

:

Two actuators are to be operated in Split Range version. Actuator 1 must be in
position CLOSED with a nominal value signal E1 of 0 mA and in position OPEN
with a signal of 10 mA.
Actuator 2 must be in position CLOSED with a nominal value signal of 10 mA
and in position OPEN with a signal of 20 mA.

.

Positioner actuator 1:
Supply E1 = 0 mA, set with P5 = 0 V at M3 (measured against MP1),
supply E1 = 10 mA, set with P6 = 5V at M9 (measured against MP1).

.

Positioner actuator 2:
Supply E1 = 10 mA, set with P5 = 0 V at M3 (measured against MP1),
supply E1 = 20 mA, set with P6 = 5V at M9 (measured against MP1).

.

Perform adjustments and settings for E2, etc. Afterwards the nominal value E1
can be transmitted through both actuators (connected in series). When oper-
ating within range E1 = 0 – 10 mA, actuator 1 moves, actuator 2 remains in
end position CLOSED. When operating within range
E1 = 10 – 20 mA, actuator 2 moves, actuator 1 remains in end position OPEN.

48

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Operation instructions

Figure AK: Positioner board A7, Split Range version

Meas.points

Meas.points

E1

{

E2

{

P9 (

Δ

E)

P7 (Sens)
P3 (0)
P4 (max)

P6
P5

S3-7

S2-7

S1-7

V10 (red)

P10

V18 (red)

V27 (yellow)

V28 (green)

M3

M9