Introduction, Installation – Dialight HZC022501111312 SafeSite LED Area Light (GenI) User Manual

Page 2

Advertising
background image

Document No: 9100-127-1376-99 Rev A

Page 2 of 5

1501 Route 34 South, Farmingdale, NJ 07727

Tel: (732) 919-3119 Fax: (732) 571-5778 www.dialight.com

1: Introduction

This area light is designed for illumination of hazardous locations. It uses the latest in solid state lighting technology for
long life, low maintenance, and high efficiency.

The unique optical design focuses light downward to where it is needed, giving improved efficiency over a conventional
HID luminaire.

An internal power-factor-corrected switch-mode supply allows it to be used from any nominal 120V-277V, 50/60Hz AC
supply without any variation in light output.

The fixture has an IP66 (ingress protection) rating and meets NEMA 4X enclosure ratings.

This lamp is suitable for use in the following locations:

UL844 Class 1 Division 2, Groups A, B, C, D; T4A temperature rating

UL844 Class 2 Division 2, Groups F and G

UL1598 wet locations & UL1598A marine locations

Indoor and outdoor non-hazardous locations


Note: Save these instructions for future reference.


2: Installation

Warning:

To avoid the risk of fire, explosion, or electric shock, this product should be installed, inspected, and maintained by a
qualified electrician only, in accordance with all applicable electrical codes.

Warning:

To avoid electric shock:

Be certain electrical power is OFF before and during installation and maintenance.

Luminaire must be connected to a wiring system with an equipment-grounding conductor.

Warning:

To avoid explosion:

Make sure the supply voltage is the same as the rated luminaire voltage.

Do not install where the marked operating temperatures exceed the ignition temperature of the hazardous atmosphere.

Do not operate in ambient temperatures above those indicated on the luminaire nameplate.

Use proper supply wiring as specified on the luminaire nameplate.

Keep covers tightly closed when in operation. No user serviceable parts inside.

For supply connections use wire rated for at least 110

º

C.

Recommended mounting height: 8 feet to 24 feet (2.4 m to 7.3 m)

Advertising