4 operating limits, Operating limits – DE DIETRICH ROE-II _ ROE-H User Manual
Page 11
11
13/01/2011 - 300019360-001-I
ROE-II / ROE-H
3.2.4
Operating limits
Heating mode ROE-II
Minimum water return temperature for start-up : +5 °C
Minimum water return temperature when operating :
- Water/glycol (antifreeze): +5 °C
- Pure water: +20 °C
Maximum water inlet temperature : 70 °C
Heating mode ROE-H
Minimum water return temperature for start-up : +5 °C
Minimum water return temperature when operating :
- Water/glycol (antifreeze): +5 °C
- Pure water: +20 °C (Underfloor heating), +25 °C (Radiator)
Maximum water inlet temperature : 60 °C
ROE-II: Cooling mode (except QUADROPAC /
OECOSUN-R 500)
Maximum water return temperature for start-up: 30 °C
Water outlet temperature (°C)
Outside temperature (°C)
30 % glycol mix
Pure water
Water outlet temperature (°C)
Outside temperature (°C)
30 % glycol mix
Pure water
0
20
-15
20
20
54
43
M001663-B
25
48
60
65
-20 -15-12
25
45
2
1
4
3
Water outlet temperature (°C)
Outside temperature (°C)
30 % glycol mix
Pure water