Conditions of use:
Limit operating temperatures in Hot mode:
- Water: +25 °C / +65 °C
- Outside air: -20 °C / +45 °C

(1)

Hot mode : Outside air temperature: +7 °C,
Water temperature at the outlet: +35 °C

(2)

Optional package EH87 to limit start-up intensity

(3)

5 m from the appliance, 1.5 m from the ground, free field, direction
factor 2.

(4)

except QUADROPAC / OECOSUN-R 500

ROE

13 MH

13 TH

17 TH

(4)

package

EH 123

EH 124

EH 125

Output

Calorific output

(1)

kW

13.52

13.46

19.06

COP hot

(1)

3.48

3.93

3.8

Absorbed electrical power

kWe

3.89

3.43

5.02

Nominal water flow

m

3

/h

2.4

2.4

3.3

Water resistance (Nominal water flow)

mbar

100

100

115

Air flow rate

m

3

/h

5100

5100

5940

Electrical connection
Power supply voltage

V

230 V ~

400 V 3~

400 V 3~

Nominal amperage

A

33.2

14.22

16.8

Start-up amperage

A

45

(2)

64

(2)

70

(2)

Miscellaneous
Sound output

dBA

69

69

78

Sound pressure level at 5 m

(3)

dBA

47

47

56

R 407 C refrigerant

kg

3.95

3.95

3.95

Weight (empty) - outside unit

kg

126

126

143

Weight (empty) - Indoor module

kg

72

72

72