Roe-h – DE DIETRICH ROE-II _ ROE-H User Manual
Page 7
7
13/01/2011 - 300019360-001-I
ROE-II / ROE-H
ROE-H
Conditions of use:
Limit operating temperatures in Hot mode:
- Water: +25 °C / +65 °C
- Outside air: -20 °C / +45 °C
(1)
Hot mode : Outside air temperature: +7 °C,
Water temperature at the outlet: +35 °C
(2)
Optional package EH87 to limit start-up intensity
(3)
5 m from the appliance, 1.5 m from the ground, free field, direction
factor 2.
(4)
except QUADROPAC / OECOSUN-R 500
ROE
13 MH
13 TH
17 TH
(4)
package
EH 123
EH 124
EH 125
Output
Calorific output
(1)
kW
13.52
13.46
19.06
COP hot
(1)
3.48
3.93
3.8
Absorbed electrical power
kWe
3.89
3.43
5.02
Nominal water flow
m
3
/h
2.4
2.4
3.3
Water resistance (Nominal water flow)
mbar
100
100
115
Air flow rate
m
3
/h
5100
5100
5940
Electrical connection
Power supply voltage
V
230 V ~
400 V 3~
400 V 3~
Nominal amperage
A
33.2
14.22
16.8
Start-up amperage
A
45
(2)
64
(2)
70
(2)
Miscellaneous
Sound output
dBA
69
69
78
Sound pressure level at 5 m
(3)
dBA
47
47
56
R 407 C refrigerant
kg
3.95
3.95
3.95
Weight (empty) - outside unit
kg
126
126
143
Weight (empty) - Indoor module
kg
72
72
72