Section 3 Operation

Models SLA5810 and SLA5820

Installation and Operation Manual

X-PR-SLA5800-PC-eng

Part Number: 541B091AAG

July, 2010

3-5 Communications Features

3-5-1 DeviceNet Communications Features

The Brooks SLA5800 Digital Series is also available with DeviceNet

TM

communication capability. DeviceNet is an open digital protocol capable of
high speeds and easy system connectivity. Brooks Instrument has several
of its devices available on this popular networking standard, and is a
member of ODVA

TM

(Open DeviceNet Vendors Association), the governing

standard body for DeviceNet.
DeviceNet

is a multi-drop connection that allows a maximum of 64 devices

to be connected on the same network. Baud rate selections for DeviceNet
products are 125K, 250K and 500K and can be selected via MAC ID
switches mounted on the device.
The DeviceNet

communication link also provides access to many of the

Brooks SLA5800 Digital Series functions for “control and monitor”
operations, including:

Accurate setpoint adjustment and flow output measurement (including
units of measure selection)

PID Settings (controller only)

Valve Override (controller only)

Calibration Gas Select

Soft Start Control (controller only)

3-5-2 F

OUNDATION

Fieldbus Communications Features

The Brooks SLA5800 Digital Series is supporting F

OUNDATION

® Fieldbus

communication protocol. F

OUNDATION

® Fieldbus is a digital network allowing

usage of existing 4-20mA cables, avoiding costly re-wiring. Fully certified
by passing ITK, this device has passed several Interoperability
requirements over a broad range of hosts. When combined with DeltaV
and using the power of PlantWeb, those devices provide intelligent alerts
allowing accurate device maintenance and service.

• Value Range check - Part of the standard function blocks
• Temperature sensor connection - Check sensor connection
• Firmware checksum - Check for Internal firmware integrity
• Non-volatile memory - Check for non-volatile memory integrity
• RAM - Check for RAM integrity
• Zero Drift/Valve Leak-by - Check for flow leak-by or sensor zero drift
• Device Overhaul due - Preventive Maintenance
• Calibration Due - Preventive Maintenance
• Valve spring life - Preventive Maintenance
• No Flow - No flow detected when setpoint requested
• Reverse Flow - Reverse flow detected
• Flow Totalizer - Informed when a user define amount of fluid has been

delivered

• Time Totalizer - Informed when a user define amount of time has

expired