Section 1 Introduction

Models MT 3809 & 3819

Installation and Operation Manual

X-VA-MT3809-3819-eng

Part Number: 541B049AHG

September, 2008

In operation the microprocessor transmitter converts the measured
process flow into a 4-20mA output with HART protocol. The signal
originates when the float magnet inside the metering tube passes a
magnetic sensor mounted on the transmitter. Flow rate information may
be viewed locally at the meter scale or displayed remotely (along with other
flow data) as a function of external support systems through analog/pulse
outputs or multiple digital communications.

In addition to transmitter features, this unit can also be ordered with
optional alarms and pulse output provided by open collector switches. One
or two alarms may be programmed prior to shipment of the unit or at the
customer site with a hand-held communicator.

C. Specifications - SMM Microprocessor
Transmitter with or without Alarm and Pulse
Output

EMC Directive 89/336/EEC: EN 50081, EN 50082
and EN 61326-1

Hazardous Location Classification
Enclosure: Type 4X/ IP65
Ambient Temperature: -22°F> Tamb < 150°F (-30°C
> Tamb < 65°C)

Intrinsically Safe
United States and Canada UL Listed, E73889, Vol. 1,
Sect. 15
Class I, II and III, Division 1, Groups A, B, C, D, E, F,
and G; T4

Europe – KEMA 01ATEX1235 X

II 2 G EEx ia IIC T4
II 2 D T135

o

C

Entity Parameters (Transmitter):
Ui=Vmax=30 Vdc; Ii=Imax=140 mA; Ci= 15 nF; Li=
0 mH

Entity Parameters (Integral Alarms):
Ui=Vmax=30 Vdc; Ii=Imax=45 mA; Ci= 0 nF; Li= 0
mH