Section 1 Introduction

Models MT 3809 & 3819

Installation and Operation Manual

X-VA-MT3809-3819-eng
Part Number: 541B049AHG
September, 2008

Non-Incendive
United States and Canada UL Listed, E73889, Vol. 1, Sect. 15
Class I, II, III, Division 2, Groups A, B, C,D F, and G; T4

Europe – KEMA 01ATEX1236

II 3 G EEx nA II T4
II 3 D T135

o

C

Explosion- proof/ Flame-proof
United States and Canada UL Listed, E73889, Vol. 1, Sect. 14
Class I, Division 1, Groups C, D;
Dust Ignition-proof, Class II, Division 1, Groups E, F, G; Class III; T4

Europe – KEMA 01ATEX2207 X

II 2 G EEx d IIB T4
II 2 D T135

o

C

Power Supply and Maximum Load Resistance
21.0 to 33.5 Vdc Power Supply, refer to Figure 1-2 below.
Input Power: Derived from Analog Output
(2-wire current loop transmitter)

Output Signals
Transmitter: 4-20 mA analog output with HART

Update Rate: 4 times per sec.
Range: 3.8 to 22.0 mA

Figure 1-2 Power Supply vs. Maximum Load Resistance

Note: Load resistance should also include I.S. barrier
resistance. When using Model 275 HART Communicator the
minimum load resistance is 250 ohms.