Burkert Type 2301 User Manual
Page 32

32
Maintenance, cleaning
note!
damage to the seat seal or the seat contour!
▶ When installing the actuator, ensure that the valve is in open
position.
→
control function a:
Without unit control: pressurize the pilot air port 1 with com-
pressed air (5 bar): valve opens.
With unit control: open the valve according to the operating
instructions for the control unit.
→
Screw actuator into the valve body.
Observe tightening torque (see “Tab. 11: Tightening torques of
valve body / nipples”).
1
2
Pilot air port
Fig. 19: Connections
tightening torques of valve body / nipples
dn
tightening torques [nm]
10/15
45 ±3
20
50 ±3
25
60 ±3
32
65 ±3
40
50
70 ±3
65
100 ±3
80
120 ±5
100
150 ±5
Tab. 11: Tightening torques of valve body / nipples
If the position of the pilot air ports for installation of the hoses
is unfavorable, these can be aligned steplessly by rotating
the actuator through 360°.
The procedure is described in the chapter entitled “8.3.4
Rotating the actuator”.
english
Type 2301