Malfunctions

11

malfuncTiOns

malfunction

remedial action

Actuator does
not switch

Pilot air port interchanged

15)

CFA

→

Connecting pilot air port 1

CFB

→

Connecting pilot air port 1

CFI

→

Pilot air port 1: Open
Pilot air port 2: Close

Pilot pressure too low

→

Observe pressure specifications on the
type label

Medium pressure too high

→

Observe pressure specifications on the
type label

Flow direction reversed

→

Observe direction arrow on the body

Tab. 16: Malfunctions - 1

15)

See diagram “Fig. 15: Pneumatic connection” in the chapter of
the same name.

malfunction

remedial action

Valve is not
sealed

Dirt between seal and valve seat

→

Installing dirt trap

Seat seal worn

→

Installing a new control cone

Flow direction reversed

→

Observe direction arrow on the body

Medium pressure too high

→

Observe pressure specifications on the
type label

Pilot pressure too low

→

Observe pressure specifications on the
type label

Valve is leaking
on the release
bore

Packing gland worn

→

Replacing packing gland

Tab. 17: Malfunctions - 2