English, 5 parameters – Burkert Type TAT002 User Manual
Page 12

10 - 0911
english
2.5
Parameters
Control
Hy1
Hysteresis 1
Switch hysteresis of Set-value 1 with
positive or negative values. The default
range is dependent on the input type.
The parameter may not be entered as
zero. The control function is predefined
with S1C.
Hy2
Hysteresis 2
Switch hysteresis of Set-value 2 with
positive or negative values(as Hy1).
The control function is predefined with
S2C.
LS1
Lowest set-value setting
Set-value limits 1 for operator
LS2
Lowest set-value setting
Set-value limits 2 for operator
US1
Highest set-value setting
Set-value limits 1 for operator
US2
Highest set-value setting
Set-value limits 2 for operator
S1C
Control function 1
in = inverted (Heating, humidifying)
dir = direct (cooling, dehumidifying)
S2C
Control function 2
in = inverted (heating, humidifying)
dir = direct (cooling, dehumidifying)
AC
Minimum switch-off period
0 ... 250 sec relay switch-off period
ouc
Dependency of the
diP = dependent
set-values
ind = independent
on
Minimum switch-on period
0...250 sec relay switch-on period
ono
Minimum delay
0...120 min; minimum delay between two
activations of the control relay.
Alarms
ALC
Configuration
rE = relative to the set-value (in Kelvin)
Temperature alarm
Ab = absolute values (in °C)
ALL
Low temperature alarm
If SET - ALL is undershot, a low
temperature alarm will be triggered after
the delay time ALd.
ALU
Over-temperature alarm
If SET + ALU exceeded, a high
temperature alarm will be triggered after
delay time ALd.
ALd
Alarm delay
0...999 min; Minimum time in which the
at temperature
conditions for an alarm situation
Overshoot/Undershoot
must be present.