English – Burkert Type TAT002 User Manual
Page 13

0911 - 11
english
Alarms
ALH
Hysteresis for the
Automatic alarm acknowledgement:
Limit value alarms
With high alarm undershot by
ALL and ALU
ALU - ALH and with low alarm with
under shooting of ALL + ALH
dAO
Alarm delay at
0...23.5 hours; suppression of
with Mains ON
Alarms after commissioning.
So1
Status of Control Relay 1
oFF = opened
with sensor fault
on = closed
So2
Status of Control Relay 2
oFF = opened
with sensor fault
on = closed
tbA
Status of the control relay
oFF = Relay deactivated
after acknowledgement by
on = Relay activated
of an alarm situation
AS
Configuration of the alarm
cL = Terminal 5-6 closed
relay at an alarm
oP = Terminal 5-6 closed
Measured value display
LCI
Lower analog
scaling of the lower display value at
Display value
Current input 4 mA or at
(-1999...1999)
Voltage input 0 V (only for the
inputs 0-20 mA, 0-1V, 0-10 V)
UCI
Upper analog
Scaling of the upper display value at
display value
current input 20 mA or with voltage
(-1999...1999)
input 1 V and 10 V (only for the
inpits 0-20 mA, 0-1V, 0-10 V)
OPb
calibration of the sensor
regardless of the measurement range
rES
Resolution
in = only whole numbers
dE = also tenths
ce = hundreths
UdM
Units
Display of the units directly in the
illuminated display. Regardless of which
controller type is being used:
see
General description
PbC
Type of sensor
Type of inout
Temperature sensor U):
J = Thermoelement „J“; Pt = Pt100;
C = Thermoelement „K“; Ptc = PTC;
S = Thermoelement „S“; ntc = NTC
current/voltage input
cur = 4...20 mA; 0-1 = 0...1 V;
(AU)
10 = 0...10 V
P3F
Third terminal of a
(if present)
Pt100 sensor
no = Pt100 2-wire wired
yES = Pt100 3-wire wired