2.3
Before the installation
PREDEFINE THE SENSOR TYPE
Hold down the SET +
buttons for 3 seconds.
Select the parameter Pbc (sensor type) and then
confirm with the SET button to see the current
default.
Type TU (temperature controller):
J = Thermoelement J; Pt = Pt100;
C = Thermoelement K; Ptc = PTC;
S = Thermoelement S; ntc = NTC
Type AU
(control devices with voltage/current input):
cur = 4...20 mA; 0-1 = 0...1 V; 10 = 0...10 V
Confirm the default with the SET button.
Briefly switch off the power to the device.
The configurable input type is noted on the controller
label. Please enter this input type if it does not
corresponds to the connected sensor type.
LOCKING AND UNLOCKING THE KEYPAD
Hold down the buttons
and
for at least 3
seconds. The POF message appears on the
display
. The keyboard is locked. The POF
message also appears if you hold down a button for
longer than 3 s.
The keyboard will be unlocked if you hold down
the buttons
and
for 3 s. POn appears in the
display for a few seconds.
CHANGING THE DEFAULT PARAMETERS
Enter a desired value with SET +
or
.
Then confirm with the SET button.
Enter a desired parameter with
or
.
NOTE
All the parameter values can only be seen by repeatedly
pressing the SET1 buttons.