English, 4 ampl - setting the amplification kp – Burkert Type 8625 User Manual

Page 27

Advertising
background image

8625-2 Standard - 25

english

6.6.4

AMPL - setting the amplification Kp

Î Select the amplification factor K

P

in a range from 0.00 to 10.00 %/K (factory

setting: 1.00). If it is attempted to set a higher value, the display will jump
automatically to 0 and a value must be entered within the range.

Setting aid:

If excessive overshoot occurs at the value of K

P

set or the control

becomes unstable, you should decrease K

P

.

On the other hand, unsatisfactory control dynamics may be improved by
raising K

P

as long as the abovementioned instability does not occur.

increase digit

next digit

2 s

set decimal point

Fig.: Setting the amplification K

P