Operating voltage

24 V DC

Power consumption

max. 0.3 W (without proportional valve)

Output current (to valve)

max. 1.0 A

Operating temperature

- 10 °C ... + 60 °C / 14 °F ... 140 °F

Interference resistance

to EN50082-2

Interference emission

to EN50081-2

Inputs

Sensor input

PT100

temperatur range

- 50 °C ... 150 °C / - 58 °F ... 302 °F

resolution

0.25 °C or 0.45 °F

1)

precision

1.5 °C bzw 2.7 °F

1)

1 standard signal input

4 - 20 mA / 0 - 10 V, adjustable

resolution

10 Bit

input impedance (4 - 20 mA)

< 200

input impedance (0 - 10 V)

> 300 k

Output

PWM output

24 V - pulse width modulated

Controller

Control algorithm

PI control

Scan time T

A

50 ms

Amplification factor K

p

0,00 - 10,00 %/K

Reset time T

N

0,1 - 200,1 s

Scaling

-50 °C ... 150 °C or -58 °F ... 302 °F

Housing

Cable outlet

rotatable in 90° steps

System of protection

IP 65

Material

polyamide

Dimensions (WxHxD)

54 x 54 x 61 mm

Order no.

143 571

1)

Calibrated to 1 m conductor length and 0.5 mm² conductor cross-section.