Error messages – Burkert Type 8791 User Manual

Page 31

Advertising
background image

31

Operating

9.4.

error messages

9.4.1.

error messages in manual and auTOmaTic operating
status

Display

Cause of fault

remedial action

LED 3 (red,
FAULT) on

Checksum error in data memory
→ Data memory defective
→ The device automatically switches to an older

(possibly not current) data record.

not possible, device defective.

Contact your Bürkert sales office.

Table 12:

Error messages in MANUAL and AUTOMATIC operating status

9.4.2.

error messages while the X.TUNE function is running

Display

Cause of fault

remedial action

LED 3 (red,
FAULT) on

No compressed air connected

Connect compressed air

Compressed air failure during the

X.TUNE

Check compressed air supply

Actuator or control system deaeration side
leaking

not possible, device defective

Control system aeration side leaking

not possible, device defective

The angular range of the position sensor
exceeds 180°

Correct the attachment of the shaft for the
position sensor on the actuator
(see chapter “11.2.2” and “11.3.2”).

Table 13:

Error messages while the X.TUNE function is running