Attachment and assembly

11.4.2. connection and start-up of the remote-sensor Type 8798

Warning!

risk of injury from improper start-up!

• Start-up may be carried out by authorised technicians only and with the appropriate tools!

risk of injury from unintentional activation of the system and an uncontrolled restart!

• Secure system from unintentional activation.

• Following assembly, ensure a controlled restart.

→

Connect the 4 wires of the sensor cable to the designated screw-type terminals of the positioner
(see chapter “13.3.6. Terminal assignment for external position sensor
(for remote model only)”).

→

Attach remote sensor on the actuator.
The correct procedure is described in the brief instructions for the remote sensor.

→

Connect positioner pneumatically to the actuator.

→

Connect compressed air to positioner.

→

Switch on supply voltage to the positioner.

→

Run the

X.TUNE function.