Electrical connection

13.3. electrical connection with cable gland

13.3.1. Designation of the screw-type terminals

11 +

12 –

81

82

31 +

32 –

A

B

+

+24 V

GND

remote

sensor

Figure 26:

Designation of the screw-type terminals

13.3.2. connection of the screw-type terminals

Unscrew the 4 screws on the housing cover and remove the cover.
The screw-type terminals are now accessible.

Connect terminals according to the configuration.

13.3.3. Terminal assignment for input signals from the control

centre (e.g. plc)

terminal

configuration

On the device side

external circuit / signal level

11 +

Set-point value +

11 +

+ (0/4 – 20 mA)
not galvanically isolated

12 –

Set-point value GND

12 –

GND set-point value

81 +

Binary input +

81 +

+

0 – 5 V (log. 0)
10 – 30 V (log. 1)

82 –

Binary input –

82 –

GND (identical with the GND supply
voltage)

Table 26:

Terminal assignment; input signals of the control centre

english

Type 8791