Electrical connection

13.3. electrical connection with cable gland

13.3.1. Designation of the screw-type terminals

11 +

12 –

81

82

31 +

32 –

A

B

+

–

+24 V

GND

remote

sensor

Figure 26:

Designation of the screw-type terminals

13.3.2. connection of the screw-type terminals

→

Unscrew the 4 screws on the housing cover and remove the cover.
The screw-type terminals are now accessible.

→

Connect terminals according to the configuration.

13.3.3. Terminal assignment for input signals from the control

centre (e.g. plc)

terminal

configuration

On the device side

external circuit / signal level

11 +

Set-point value +

11 +

+ (0/4 – 20 mA)
not galvanically isolated

12 –

Set-point value GND

12 –

GND set-point value

81 +

Binary input +

81 +

+

0 – 5 V (log. 0)
10 – 30 V (log. 1)

82 –

Binary input –

82 –

GND (identical with the GND supply
voltage)

Table 26:

Terminal assignment; input signals of the control centre

english

Type 8791