Dir.cmd – Burkert Type 8791 User Manual
Page 33
33
Functions
10.1.1. DIR.CMD -
effective sense of direction of the position controller set-
point value
Use this function to set the effective sense of direction between the input signal (INPUT) and the set-point
position of the actuator.
Factory settings: DIP switch set to OFF (ascending)
DiP switches Position
Function
1
ON
Reversal of the effective sense of direction of the set-point value
(
DIR.CMD)
Set-point value (20 – 4 mA corresponds to position 0 – 100 %),
descending
OFF
Normal effective sense of direction of the set-point value
(Set-point value 4 – 20 mA corresponds to position 0 – 100 %),
ascending
Table 16:
DIP switches 1
The effective sense of direction (
DIR.CMD) can be changed only via DIP switch 1 in the positioner.
Set-point position
Input signal
(
INPUT)
ascending
descending
Figure 12:
DIR.CMD graph
english
Type 8791