Installation

Type 8025/8035 /

→

Install the device on the pipe in such a way that the upstream and
downstream distances are respected according to the design of
the pipes, refer to standard EN ISO 5167-1 and "Fig. 4":

flow direction

50 x DN 5 x DN

40 x DN 5 x DN

25 x DN 5 x DN

20 x DN 5 x DN

18 x DN 5 x DN

15 x DN 5 x DN

With control valve

Pipe with 2 elbows at 90° in 3

dimensions

Pipe with 2 elbows at 90°

Pipe with 1 elbow at 90° or 1

T-piece

With pipe expansion

With pipe reduction

Fig. 4: Upstream and downstream distances depending on the

design of the pipes

→

Ensure that the pipe is always filled in the section around the
device (see "Fig. 5").

→

When mounting vertically ensure that the flow direction is in an
upward direction (see "Fig. 5").

Horizontal mounting

Correct

Incorrect

Vertical mounting

Correct

Incorrect

flow direction

Fig. 5: Filling of the pipe

→

Prevent the formation of air bubbles in the pipe in the section
around the device (see "Fig. 6").