Wiring

Type 8025/8035 /

8.6.2. Wiring the 8025, remote version, 12-36 V Dc, with relays

→

For a wall-mounted version, obey the wiring instructions of chap. "8.7.1".

→

Before wiring the device, configure the selectors on the electronic board (see chap. "8.3").

→

Connect the flow sensor to the transmitter according to chap. "8.5".

Supply

12..36Vdc

FLOW SENSOR

COIL

NPN

L+

L-

PE

P-

P+

NC

L+

L-

PE

P-

P+

Iout

PULSE

OUTPUT

Without

With

Relays

NPN SENSOR

1 PULSE INPUT

2 -

3 +

4 NC

SUPPLY

1

2

3

4 PE

REL1

REL2

COIL SENSOR

1

2

3 NC

4 NC

4

6

3

5

A

2

1

B

PE

Switch A : see chap. "8.3.1"

Switch B : see chap. "8.3.2"

terminal block 1
Iout: 4-20 mA output
L+: positive power supply
L-: negative power supply
PE: wiring of the PE between the main board and the protection
board
P-: negative pulse output
P+: positive pulse output

terminal block 2 pe
Wiring of the cable shields

terminal block 3: wiring of relay 1, see chap. "8.4.2"
terminal block 4: wiring of relay 2, see chap. "8.4.2"
connector 5: connection of the flow sensor see chap. "8.5"
Jumper wire 6: jumper wire to be removed if the 4-20 mA output is
connected

Fig. 38: Terminal assignment of a panel-mounted or wall-mounted version, 12-36 V DC, with relays