Wiring

Type 8025/8035 /

8.4.5. Wiring the 8025 compact version and the 8035, 115/230V Dc, without relays, with cable glands

→

Before wiring the device, configure the selectors on the electronic board (see chap. "8.3").

The red wire is wired on the NC terminal to make the wiring of the
4-20 mA output easier (see "Fig. 30"). The jumper wire 4 between L+ and
NC energizes the NC terminal.

Supply

12..36Vdc

FLOW SENSOR

COIL

NPN

L+

L-

PE

P-

P+

NC

L+

L-

PE

P-

P+

Iout

PULSE

OUTPUT

Without

With

Relays

230V

T 125 mA

N

PE

L

{

3

5

6

7

4

A

2

1

B

PE

Switch A : see chap. "8.3.1"

Switch B : see chap. "8.3.3"

terminal block 1
NC: not connected (terminal for the wiring of the
4-20 mA output)
L+ (red wire, factory wired)
PE: wiring of the PE between the main board and the
protection board
L- (black wire, factory wired)
P-: negative pulse output
P+: positive pulse output

terminal block 2 pe
Shield connection (green/yellow wire, factory wired)

connector 3: connection of the flow sensor
Jumper wire 4: jumper wire to be removed if the
4-20 mA output is connected

time-delay fuse 5: fuse to protect the 115 V AC or
230 V AC power supply
earth terminal 6 of the housing: internally connected
to the earth plug
terminal block 7: wiring of the 115/230 V AC power
supply

Fig. 29: Terminal assignment of a 115/230 V AC compact version without relays, with cable glands