DS 50 / DS 50 LC +030222065 Rev. 1.2

13

Airflow 1000 cfm min.

Airflow

Min 8”

Height >8”

=

=

Airflow

1000 cfm min.

1/3 Height

Airflow

1000 cfm min.

=

=

8” min

24” min
Upstream

36”min
Downstream


IMPORTANT: Allow 1 M ( 3 feet ) of straight duct downstream of the distributor pipes and nozzles for absorption of the steam.
Always allow 0.6M (2 feet) of straight duct upstream of the distributor pipes for evaporation of the steam. Turbulent air flow may
require longer lengths

.





3.4.2

Return Condensate Connection

The return condensate hose from the manifold must be trapped. Coil the hose
into a vertical loop and secure it below the manifold. This water trap prevents
steam from being released into the hose. Insert the barbed fitting into the end
of the hose. Route the manifold drain hose through the top of the humidifier,
into the top of the fill cup. This is just above and to the right of the steam
cylinder. See. Fig. 3.l




































Fig. 3.k

Fig. 3.l