DS 50 / DS 50 LC +030222065 Rev. 1.2
24
8. TECHNICAL SPECIFICATIONS
Steam flows, VAC, kW
20 lbs/hr (9 kg/h): 230 VAC 1-phase 50-60 Hz, 6.9 kW
Notes
Outlet pressure limits
5.4 in WC / 1350 Pa
For duct only
Dimensions (mm )
31” x 18” x 11.4” (790 x 460 x 290 mm)
(Height x Width x Depth)
Weight empty/packaged/installed
with water
24/29/51 lbs. (11/13/23 kg)
IP class
IP20
Electrode power cables
8 AWG
Power contactor
63 Amp
Ground connection
Terminal block
Input water type
Potable water
no demin. or softened water
Conductivity range
125-1250 µS/cm
Special cylinders for cond. < 350
µS/cm
Water fill connection
1/4” O.D. Compression
Adapter to ¾” FPS
Water fill - instant flow
0.22 – 0.3 gpm
(0.825 – 1.1 l/min)
Drain connection
1.25” O.D. (32 mm)
Adjustable from horizontal to vertical.
May be from back or bottom of unit.
Drain water temp
< 140°F
(< 60°C)
drain tempering device
Drain flow
Max 5.1 gpm
(max 21 l/min)
Serial communication
RS485