Technical specifications – GeneralAire DS50 LC Elite Steam User Manual

Page 24

Advertising
background image

DS 50 / DS 50 LC +030222065 Rev. 1.2

24

8. TECHNICAL SPECIFICATIONS

Steam flows, VAC, kW

20 lbs/hr (9 kg/h): 230 VAC 1-phase 50-60 Hz, 6.9 kW

Notes

Outlet pressure limits

5.4 in WC / 1350 Pa

For duct only

Dimensions (mm )

31” x 18” x 11.4” (790 x 460 x 290 mm)

(Height x Width x Depth)

Weight empty/packaged/installed
with water

24/29/51 lbs. (11/13/23 kg)

IP class

IP20

Electrode power cables

8 AWG

Power contactor

63 Amp

Ground connection

Terminal block

Input water type

Potable water

no demin. or softened water

Conductivity range

125-1250 µS/cm

Special cylinders for cond. < 350
µS/cm

Water fill connection

1/4” O.D. Compression

Adapter to ¾” FPS

Water fill - instant flow

0.22 – 0.3 gpm

(0.825 – 1.1 l/min)

Drain connection

1.25” O.D. (32 mm)

Adjustable from horizontal to vertical.
May be from back or bottom of unit.

Drain water temp

< 140°F

(< 60°C)

drain tempering device

Drain flow

Max 5.1 gpm

(max 21 l/min)

Serial communication

RS485






































Advertising
This manual is related to the following products: