3.6.1

Connect the GFX50 Humidistat for Modulating operation

Connect Elite Steam terminals 24V and GND to GFX50 terminals GO5 and G6
respectively. Do not reverse these connections. Connect GFX50 terminal A OUT 6
to Elite Steam terminal IN. See fig. 3.t.
NOTE:

1. MODULATING OPERATION requires Elite Steam signal type be changed,

SEC. 5.1.1 page 19

2. The GFX50 is capable of ON-OFF operation. See the GFX50 manual.
3. The GFX50 is capable of Outdoor Temperature Compensation see the

GFX50 manual.

4. The GFX50 is designed to wall mount. It is not intended for duct

installation.

5. Reversing the 24V and GND leads will result in humidifier malfunction.







3.6.2

Connect the E2 Humidistat ON-OFF Operation

Connect Elite Steam terminals 24V and GND to E2 terminals ACL, ACN. Connect E2
terminals HUM to Elite Steam terminals GND and IN.
NOTE:

1. To remove humidistat from the base, squeeze the louvered base at the top

and bottom. To remove from wall, lift up on the humidistat and pivot top
away.

2. Terminal block may be pulled off humidistat for easy connecting.
3. The E2 is capable of Outdoor Temperature Compensation see E2 manual.
4. The E2 may be wall or duct mounted.











3.6.3

Air pressure, Safety and High Limit Switches

Remove the jumper between terminals AB-AB and connect 12500 pressure switch,
High Limit Humidistat, safety switch or remote contact in series. If none are to be
installed the jumper must remain in place. DO NOT apply any voltage to AB-AB.


3.6.4

Air Conditioner Relay Interlock

Auxiliary DPDT safety relay: Use this method in the following situations:
1. To prevent the air conditioner from running when there is a call from humidity.
The DPDT relay will open the “Y” circuit and close the “G” circuit for operation while
a call for humidity is present. Demand for humidity will override call for cooling.
2. In systems using a thermostat where G and Y are a single circuit. The DPDT
relay will allow blower operation to occur without back-feeding the compressor.
Do not use this method when simultaneous humidification and cooling will be
desired. Use a high limit humidistat in to avoid condensation in ductwork.
The humidistat should be set to OFF during the air conditioning season if
humidification is not desired.
For variable speed or DC systems, consult furnace manufacturer.


Thread control wiring through the bottom of the unit and the strain relief (Fig. 3.m and 3.n) then up the side of the control module to
the wiring terminal blocks.




Fig. 3.t

Fig. 3.u

Fig. 3.v

Elite Steam

ON

D

IP

1 2 3 4

ON

OFF

OFF

ON

N2

GND

N1

AB

AB

GND

IN

NO

C

NC

C

NO

GND

24V

AC

L

AC N

HUM

SNSR

OUTDOOR TEMP. SENSOR
(not used in manual mode)

W

Y

R

G

C

NO

C

NC

C

NO

GND

24V

N2

GND

N1

AB

AB

GND

IN

Furnace Control Circuit Board

DPDT RELAY

(FIELD SUPPLIED)

CO

IL

2

4

V

Elite Steam

C1

NO2

NC2

NC1

C2

TO AIR

CONDITIONING

CONTACTOR

GFX50 HUMIDISTAT

E2 HUMIDISTAT

AIR CONDITIONER RELAY