5 humidistats, 6 alarms – GeneralAire DS50 LC Elite Steam User Manual

Page 20

Advertising
background image

DS 50 / DS 50 LC +030222065 Rev. 1.2

20

5.5

Humidistats

Several GeneralAire humidistats may be used with the Elite Steam Humidifier;
GFX50 (included)
Allows Modulating or On-Off operation. Is capable of Outdoor Temperature Compensation, and has other programmable functions.
Backlit LCD display.

E2 (optional)
On-Off operation only. Is capable of Outdoor Temperature Compensation. LCD display.

M3 and SCX3 (optional)
Manual, On-Off operation only.

For detailed installation, programming and operating instructions, please see the Humidistat’s Operating Manual.
WARNING: Do not allow excess humidification. Excess humidity can cause condensation and enable mold and mildew growth.

5.6

Alarms

In the event of an alarm, the red alarm LED will flash, the alarm relay will close, and the alarm code will flash in the display. Multiple
alarms will flash in sequence, alternating with the main display. Pressing the sel button for 2 seconds will reset the alarms, although
still active alarms will continue to display.

Dis

play

Description Action

Red

Led

Alarm

Relay

Notes

--

Remote on-off open

Unit disabled

Off

Off

Check Pressure Sw. circuit, AB-AB

EE

Internal memory error

Unit disabled

On

On

Contact Factory

E0

Control board configuration not valid

Unit disabled

On

On Contact

Factory

E1

High current alarm

Unit disabled

On

On

Turn off, check connections, check
cylinder (no limescale bridges between
electrodes, no electrodes short-circuited)

E2

Low production, low supply water
conductivity or excessive
foam/limescale in the cylinder

Unit disabled.
Press “reset/sel” key for 1 seconds to reset.

On

On

Check supply water conductivity (too
low?), replace the cylinder.

E4

Fill alarm, unable or slow fill
(current does not increase within
timeout)

Press “reset/sel” key for 1 seconds to reset, otherwise
the warning will be reset automatically every 10
minutes until the supply water is available again.

On

On

Check water supply and fill valve; check
drain pump for leakage

E5

Drain alarm, unable to drain
(current does not decrease within
timeout)

Press “reset/sel” key for 1 seconds to reset

On

On

Check drain pump and drain connection

E6 Cylinder

exhausted

(critical performance detected)

The warning is automatically reset if DS 50 / DS 50 LC
can produce the demand, otherwise turn off and then
on.

Off Off Change

cylinder

(urgent)

E7 Foam

detected

Press

reset/sel” key for 1 seconds to reset

Off

Off

If it continues, do some cleaning cycles
(read chap. “Starting with a new
cylinder”)

E8

Cylinder lifetime expired (2000 hours)

Reset the hour counter (read chap. Resetting the hour
counter”)

Off

Off

Change the cylinder.

E9

High controller temperature (above
176 °F / 80 °C)

The warning is automatically reset if the temperature
decreases below 176 °F / 80 °C.

Off

Off

Check the ambient temperature, replace
the controller.