3. INSTALLATION

3.1 Positioning

The Elite Steam has been designed for wall mounting and, since it is an atmospheric steam
humidifier, should be placed close to the point where the steam will be used, to minimize the
steam hose length (and the amount of condensate). Do not mount on furnace, air handler or
ductwork. Certain clearances must be maintained around the unit for safety and
maintenance
.


3.2 Mounting


3.2.1

Removing the front cover

The front cover is secured by two screws located in the bottom side of the unit. Use a phillips
screwdriver to remove the screws. The front is clasped with 2 clips on the top of the back
part. To remove the front cover, hold by the sides pivot the bottom out and lift cover. When
installing the cover, be careful not to over-tighten the screws.

screws M5x16

Fig. 3.c

Fig. 3.d

Millimeters

Inch

A

(150 mm)

6”

B

(150 mm)

6”

C

(150mm)

6”

D

(150 mm)

6”

E (600

mm)

24”

F max.

0.2°

Tab. 3.a

Fig. 3.a

Clearance Dimensions

Millimeters

Inch

A

445 mm

17.5“

B

290 mm

12“

C

790 mm

32“

Kilograms

Pounds

Weight empty

11kg

24 lbs

Weight packaged

13kg

29 lbs

Weight installed with water

23kg

51 lbs

Tab. 3.c

Unit Dimensions: Duct Units

Fig. 3.b

SCREWS M5x16