Advanced Controller Programming (Cont.)

Low Power Mode

This function is only used with DC barrier gate Model BGU-D. The
factory default disables the Low Power Mode. When Low Power Mode is
enabled, and AC power fails, the controller will assume Low Power Mode
after 60 seconds of gate inactivity. Low power mode turns off all accessory
power and indicators. Only inputs from the radio receiver, reverse loop,
open loop (optional by programming), fi re department input, or restoring AC
power will wake the Controller from Low Power Mode. Programming Mode
can still be accessed while the Controller is awake in Low Power Mode.

NOTE: This function will only be displayed in Model BGU-D operators.

Power Failure Mode

This function is only used with DC barrier gate Model BGU-D. The
factory default is set for Fail Safe, alternately the Controller can be set for
Fail Secure, Open Immediate, or Close Immediate.

• Fail

Safe: If the AC power fails and the battery voltage drops below

approximately 22 Volts, 5 seconds later the operator will cycle open
if not already open. When AC power is restored, or the battery gets
charged by solar panels, the operator will resume normal operation
and auto-close if programmed to do so.

• Fail Secure: If the AC power fails and the battery voltage drops

below approximately 22 Volts, 5 seconds later the operator will
cycle closed if not already closed. When AC power is restored, or
the battery gets charged by solar panels, the operator will resume
normal operation.

NOTE: Fail Safe and Fail Secure are disabled if Stagger Mode is enabled.

• Open Immediate: If the AC power fails, the operator will cycle

open if not already open and cease operation. When AC power is
restored, the operator will resume normal operation and auto-close
if programmed to do so.

• Close Immediate: If the AC power fails, the operator will cycle

closed if not already closed and cease operation. When AC power is
restored, the operator will resume normal operation.

NOTE: This function will only be displayed in Model BGU-D operators.

Soft Start/Stop Duration

This function is only used with DC barrier gate Model BGU-D. This
function causes the operator to start and stop the DC motor slowly
reducing gate wear and tear (at the full open or closed positions only).
The factory default sets the Soft Start/Stop Duration to 3 seconds. The
Soft Start/Stop Duration can be set from 1 to 10 seconds.

NOTE: Changing the Soft Start/Stop Duration will reset the open and

close current setting value to zero. It will be necessary to reprogram
maximum open and close current settings.

NOTE: This function will only be displayed in Model BGU-D operators

set for DC motor operation with soft start motor selection.

Reset Cycle Count

The Controller counts of the number of times the operator has been cycled
full open and close. The cycle count can be displayed. The display will
scroll the cycle count number, fl ashing two digits at a time from left to right.

To reset the Cycle Count, press and hold the ENTER button for 2 seconds
while the Cycle Count is displayed.

If the Maintenance Alert has been triggered, resetting the Cycle Count
will also reset the Maintenance Alert indicator.

FUNCTION

SET TO FAIL SAFE MODE

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

POWER

FAILURE MODE

"FS"

SET TO FAIL SECURE MODE

DC MODELS

ONLY

SET TO OPEN IMMEDIATE MODE

SET TO CLOSE
IMMEDIATE MODE

FUNCTION

SET SOFT START DURATION TIME
FROM 1 TO 10 SECONDS

SOFT START DISABLED

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

SOFT START/STOP

DURATION

"SS"

DC MODELS

ONLY

FUNCTION

PRESS ENTER TO START THE CYCLE COUNT DISPLAY

1ST DISPLAY

NOTE: PRESS ENTER FOR 2 SECONDS
WHILE THE "CT" FUNCTION IS DISPLAYED
TO RESET THE CYCLE COUNT TO ZERO

RESET CYCLE

COUNT

"CT"

2ND DISPLAY

3RD DISPLAY

4TH DISPLAY

EXAMPLE ABOVE SHOWS 10,420 CYCLES

DECIMAL POINT LIT
ON 4TH DISPLAY

FUNCTION

LOW POWER MODE DISABLED

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

LOW POWER

MODE

"LP"

LOW POWER MODE #1
RADIO WILL WAKE AND ACTIVATE,
REVERSE LOOP WILL JUST WAKE

DC MODELS

ONLY

LOW POWER MODE #2 - RADIO OR
OPEN LOOP WILL WAKE AND ACTIVATE,
REVERSE LOOP WILL JUST WAKE

THE FIRE DEPARTMENT INPUT

WILL ALWAYS WAKE UP CONTROLLER