3.6.1 ICSI 08 D1 - 8 Non-Isolated 24Vdc Inputs
Binary non isolated input unit with 8 input channels for 24 VDC. The unit has to be mounted
on a plug-in base ECZ.
Description:
Eight yellow input status led's «0» to «7»
1
«TEST» push-button .......... 2
Red error led ...................... 3
List of error codes .............. 4
Electrical Connection:
• Common “+” terminals are connected together.
• Common “+” terminals must not be used when the unit’s power supply is 24 VDC.
• Common “+” terminals may be used to supply the inputs with 24 VDC when the unit’s
power supply is 120/230 VAC.
• If an external power supply 24 VDC is used for inputs, the "0" VDC must be connected to
the common "–".
Caution: 24 VDC must never be connected to common "+".