Micromod MOD: Remote I/O Modules for use with 2020N Remote I/O Interface Module User Manual

Page 26

Advertising
background image




Remote I/O Modules

ELECTRICAL CONNECTIONS

• If an external power supply 24 VDC is used for inputs, the "0" VDC must be connected to

the common "".

ICSI16D1 120 VAC

I/O REMOTE UNIT

ABB Procontic CS 31

Unit error

Bus error

TEST

0

1

2

3

4

5

6

7

0

1

2

3

1

3

2

4

4

5

6

7

Input

8

9

10

11

12

13

14

15

Cut wire

Shield

Bus # 1

Bus # 2

Ground

I

Common -

Common -

A

B

C

D

E

F

G

H

L

M

N

O

P

Q

R

Common +

Common +

Common +

Common +

Common +

Power
Supply

230 VAC

120 VAC

Common +

Technical Characteristics:

Power supply

24 VDC

230 or 120 VAC 50 or 60 Hz

Number of inputs per unit

16

16

Power supply isolation

no

yes (1500 VAC)

Inputs opto-isolated no

no

Supply output regulated 24 VDC (± 5 %)

-

100 mA

Signal level of the input, nominal value

24 VDC

24 VDC

Signal level of the input :

0 - OFF signal

–3 to +5V

–3 to +5V

1 - ON signal

+15 to +30V

+15 to +30V

Open circuit detection*

yes

yes

Input current for 24 VDC

6 mA

6 mA

Input delay

8 ms

8 ms

Maximum power consumption

0.2 A

10 VA

Maximum power dissipation

4.5 W

8 W


* A 20 to 30 kOhm resistor must be mounted in parallel of each input captor to get open
circuit detection for that channel. With an inductive captor, the minimal current is 1 mA.

22