5 icsi 16 e1: 16 isolated 24vdc inputs, Remote i/o modules electrical connections – Micromod MOD: Remote I/O Modules for use with 2020N Remote I/O Interface Module User Manual
Page 27

Remote I/O Modules
ELECTRICAL CONNECTIONS
3.6.5 ICSI 16 E1: 16 Isolated 24Vdc Inputs
Binary isolated input unit with 16 input channels for 24 VDC. The unit has to be mounted on a
plug-in base ECZ.
Description:
Sixteen yellow input status led's «0» to «15»
1
«TEST» push-button ....2
Red error led ................3
List of error codes ........4
Electrical Connection:
• Connect one external power supply 24 VDC for inputs A-H and one for inputs I-R.
• If one external power supply 24 VDC is used for different input groups (A-D, E-H, I-L or M-
R), the "0" VDC must be connected to all commons (A-D, E-H, I-L and M-R).
3
2
4
ICSI16E1 120 VAC
I/O REMOTE UNIT
ABB Procontic CS 31
Unit error
Bus error
TEST
0
1
2
3
4
5
6
7
0
1
2
3
1
4
5
6
7
Input
8
9
10
11
12
13
14
15
Shield
Bus # 1
Bus # 2
I
Common (I-L)
Common (E-H)
Common (A-D)
A
B
C
D
E
F
G
H
Common (M-R)
L
M
N
O
P
Q
R
L1
N
PE
23