Micromod MOD: Remote I/O Modules for use with 2020N Remote I/O Interface Module User Manual
Page 35

Remote I/O Modules
ELECTRICAL CONNECTIONS
Technical Characteristics
General
Power supply
24 VDC
230 VAC/120 VAC
Number of inputs per unit
12
12
Number of outputs per unit
8
8
Isolated power supply
no
yes (1500 VAC)
Maximum consumption
0.3 A
10 VA
Inputs
Signal level of the input, nominal value
24 VDC
24 VDC
0 - OFF signal
–3 to +5V
–3 to +5V
1 - ON signal
+15 to +30V
+15 to +30V
Opto isolated inputs
no
no
Input current for 24 VDC
5 mA
5 mA
Input delay
8 ms
8 ms
Outputs
Opto isolated outputs
yes
yes
Switching capacity under 2 A (
resistive or
inductive load)
120/230 VAC 50/60Hz
2 A
2 A
DC
60 W (2A)
60 W (2A)
Nominal current
2 A AC-1
2 A AC-1
Minimum power for the contacts
12 VDC 10 mA
12 VDC 10 mA
24 VDC internal power supply
no
yes (
±5%) 100 mA
Total current Common M-Q
120/230 VAC 50/60Hz
6 A
6 A
24 VDC
6 A
6 A
Total current Common R-T
120/230 VAC 50/60Hz
4 A
4 A
24 VDC
4 A
4 A
Short-circuit protection
no
no
Over voltage protection
Varistor
Varistor
31