ELECTRICAL CONNECTIONS
ICSI16E1 24 VDC
I/O REMOTE UNIT
ABB Procontic CS 31
Unit error
Bus error
TEST
0
1
2
3
4
5
6
7
0
1
2
3
1
4
5
6
7
Input
8
9
10
11
12
13
14
15
3
2
4
Shield
Bus # 1
Bus # 2
Ground
I
Common (I-L)
Common (E-H)
Common (A-D)
A
B
C
D
E
F
G
H
Common (M-R)
L
M
N
O
P
Q
R
Technical Characteristics:
Power supply
24 VDC
230 or 120 VAC 50 or 60 Hz
Number of inputs per unit
16
16
Power supply isolation
no
yes (1500 VAC)
Inputs opto-isolated
yes (1500VAC)
yes (1500Vac)
Supply output regulated 24 VDC (± 5 %)
-
-
Signal level of the input, nominal value
24 VDC
24 VDC
Signal level of the input :
0 - OFF signal
–3 to +5V
–3 to +5V
1 - ON signal
+15 to +30V
+15 to +30V
Open circuit detection
None
None
Input current for 24 VDC
6 mA
6 mA
Input delay*
8 ms
8 ms
Maximum power consumption
0.2 A
10 VA
Maximum power dissipation
4.5 W
8 W
* After the input delay, the effective value is 13 ms.