Micromod MOD: 30ML Operation and Template Setup User Manual
Page 17

MOD 30ML Operation
SETUP
2-7
Table 2. Device Setup (Cont’d)
Step
Step Description
Line 1
Line 2
Line 6
Entry Description
2A
Setup Built-in Communications
∇ moves down to Step 2A1 if
jumper is on ICN or 2A3 if jumper
is on RS232, or RS485.
NXT, PRV change step
SETUP BI
COMM
Except for the address, built-in
communication parameters can be
changed while the instrument state
is RUN. Address changes require
that the instrument be in the
DEFAULT state (See Note) or with
port status set off after power up
and SCRV switch set (LHD or DEF
state).
2A1
Set ICN Address
∇ ∆ changes number, ENT enters.
NXT, PRV change step
BI ICN 1 ADDRESS
15
ICN address can be 0 to 15. Can
be set when the instrument is in the
DEFAULT state (See Note).
Communication jumper set on the
ICN position.
2A2
Set ICN Status Active
∇ ∆ selects YES/NO, ENT enters.
NXT, PRV change step
BI ICN 1 ENABLED
ENABLE?
NO
ENABLED = Active. To make
inactive, power up with SCRV
switch set. ENABLE? = Inactive.
Select YES to make it active.
2A3
Set Modbus Address
∇ ∆ changes number, ENT enters.
NXT, PRV change step
BI MSC 1 ADDRESS
247
Modbus address can be 1 to 247.
Can be set when the instrument is
in the DEFAULT state.
Communication jumper set on
RS232, or RS485 position.
2A4
Set Modbus Baud Rate
∇ ∆ changes rate, ENT enters.
NXT, PRV change step
BI MSC 1 BAUDRATE
9600
150, 300, 600, 1200, 2400, 4800,
9600, 19200, 38400
2A5
Set Modbus Parity
∇ ∆ changes parity, ENT enters.
NXT, PRV change step
BI MSC 1 PARITY
NONE
None. Odd, Even
2A6
Set Modbus Stopbits
∇ ∆ changes stopbits, ENT enters.
NXT, PRV change step.
BI MSC 1 STOPBITS
1
1, 2
2A7
Set Modbus Status Active
∇ ∆ selects YES/NO, ENT enters.
NXT, PRV change step
BI MSC 1 ENABLED
ENABLE?
NO
ENABLED = Active. To make
inactive, power up with SCRV
switch set. ENABLE? = Inactive.
Select YES to make it active.
2A8
Setup Communication (Exit)
∆ moves up to Step 2A.
SETUP
2B
Password
∇ moves down to Step 2B1
NXT, PRV change step
SETUP PASSWORD
2B1
Password
∇ ∆ changes number, ENT enters
and changes step
PASSWORD
0
Enter a number to change access
to the instrument to None, Tune or
Configure.
2B2
Current Level
ENT goes to step 2B.
CURRENT LEVEL
TUNE
NONE an invalid password.
TUNE tune access.
CONFIG configuration access.
2C
Setup Device (Exit)
∆ moves up to Step 2
NXT, PRV change step
SETUP *DEVICE*
NOTE: Built-in address cannot be changed if the ICN or MSC block's address within the Main Database is set to a specific number (not
set to "Any"). In order to change the address, the Main Database must first be deleted or a new Database must be downloaded which
has the ICN or MSC block's address configured to "Any".