MOD 30ML Operation

SETUP

2-16

Table 8. User Compound Template Configuration (Cont’d)

Step

Step Description

Line 1

Line 2

Line 6

Entry Description

Millivolt and Thermocouple Inputs Only:

8D14
(TC)

Process Input CJC Source

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP CJC SRC NONE

NONE, BI AIN 1, S01 TO S11

8D15
(TC)

Process Input Burnout

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP BURNOUT NONE

NONE - no burnout detection
DN SCALE - signal moves
downscale if burnout is detected.
UP SCALE. - signal moves upscale
if burnout is detected.

All Inputs:

8D16

Process Input Low Quality

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP LO QUAL -10.0

Result is set BAD if it goes below
this value.

8D17

Process Input High Quality

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP HI QUAL 110.000

Result is set BAD if it goes above
this value. High quality must be
higher than the low quality value.

8D18

Process Input Quality Alarm

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP QUAL ALM DISABLE

Disable or Enable.

8D19

Process Input Quality Digital Output

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP QA D OUT NONE

NONE or S01 to S11 location of
digital output module.

8D20

Process Input Quality Priority

∇ ∆ change value, ENT enters

NXT, PRV change step

PROC INP QA PRI

1

0 = suppress unacknowledge
1 to 255 = priority level.

8D21

Process Input (Exit)

∆ moves up to Step 8D

NXT, PRV change step

PROC INP

8E

Setpoint (Entry)

∇ moves down to Step 8E1

NXT, PRV change step

CTAG01 SETPT

8E1

Setpoint Display Format

∇ ∆ change value, ENT enters

NXT, PRV change step

SETPOINT DISP FMT FLOAT 3

Float 0 = x
Float 1 = x.x
Float 2 = x.xx and so forth to
Float 6 = x.xxxxxx

8E2

Remote Setpoint Input Setup (Entry)

∇ moves down to Step 8E2A

NXT, PRV change step

REMOTE SETPOINT

8E2A

Remote Setpoint Slot Position

∇ ∆ change value, ENT enters

NXT, PRV change step

REMSETPT SLOT NONE

None, BI AIN 1, BI AIN 2, S01 to
S11

8E2B

Remote Setpoint Input Type

∇ ∆ change value, ENT enters

NXT, PRV change step

REMSETPT INP TYPE VOLTS

Select type as: VOLTS, MVOLTS,
CURRENT, RESIST, THRMOCPL
1 Slot: RTD2WIRE, CURRNT2W
2 Slots: RTD3WIRE, WIDERES
Built-in only: TC W/CJC, RTD

8E2C

Remote Setpoint Input Setup

Same as process value inputs.

See Process Value input setup.

8E2D

Remote Setpoint Input Setup (Exit)

∆ moves up to Step 8E2

NXT, PRV change step

REMSETPT