Micromod MOD: 30ML Operation and Template Setup User Manual

Page 59

Advertising
background image

MOD 30ML Multiloop Controller

OPERATION

3-27

3.14.3 Control Parameters

The control tuning sequence is accessed from the runtime display. Enter the tuning sequence
and make tuning adjustments as follows:

1. Press the Scroll key repeatedly until [TUNE???] appears on Line 6.

2. Press the Up[

∆] key. [CONTROL] appears on Line 6 and [ENT] flashes next to the Scroll

key.


3. Press the Scroll key to start the tuning sequence.

• If a tune password is not required, a 4-letter code identifying the configured

control algorithm type appears on Line 6; go to step 4.

• If a tune password is required, [TUNE] and [PASSWORD] appear on Lines 1 and

2. Use the Up(

∆) key to enter the password number, then press scroll to access

the tune sequence. A 4-letter code identifying the configured control algorithm
type appears on Line 6.


4. Observe the 4-letter code on Line 6. The code letters identify which of the four primary

control algorithm parameters (gain, reset, preact, and manual reset) are active and how
the active parameters are implemented. For example, the code [EOPE] indicates that the
algorithm provides gain on error, reset is off, preact on process, and manual reset is
enabled (see Table 8, Step 8F for more information on Control Type setup).


*

NOTE:

The gain, reset, and preact prompts always appear in the tuning
sequence. The tuned values of these parameters are used in the control
algorithm only when their code letters are other than O.

Loop Tag

Tunable Parameter

Press to return to runtime display.

Press to return to previous display.

From [NXT], press to advance to next display.
From flashing [ENT], press to enter displayed
parameter. value.

∇/∆ adjust parameter value

Parameter value

Advertising