Installation, Insulation, System interfaces – Fulton VMP Hot Water (VMPW) User Manual

Page 18: Assembly of multi-skid systems, Fill connection, Pressure gauges

Advertising
background image

© The Fulton Companies 2012

INSTALLATION

VMPW-IOM-2012-1001

SECTION 2

2-12

suitable for use with the pressure, temperatures and fl uids in the system.
Ensure that all bolts are tightened evenly and to the torque recommended
values provided by the gasket manufacturer.

10. Install high point bleeds at all high points in the system piping. 1/2” x 12”

nipples welded in the top of the piping with ball valves and plugs attached
are to be used.

11. Install all pipes with a pitch to facilitate draining and venting.

Insulation

After the appropriate system tests have been satisfactorily completed (see
Testing section of this manual), all hot pipework and vessels must be adequately
insulated with material suited to the temperature and application to prevent
both heat loss and personnel injury. For inspection and maintenance purposes,
leave pumps, fl anges, valves and fi ttings uninsulated but suitably shielded for
safety. Removable insulation may also be used over these components.

System Interfaces

Proper selection and installation of the components in the system will ensure
proper and safe operation of the boiler. Consult Fulton representative or contact
Fulton at (315) 298-5121.

Fill Connection

The system is usually fi lled from the lowest point, with the aid of a pump. On skid-
mounted units, a fi ll connection is provided in the inlet piping to the pump.

Pressure Gauges

The range in which readings are expected to fall should comprise mid-scale
on the pressure gauge chosen. Pressure gauges must be able to withstand
overpressure equal to the rating of the safety relief valves, normally 100 psig.

NOTE: The Water temperature pressure gauge should not be altered in any way.

Assembly of Multi-Skid Systems

Adhere to the following for multi-skid engineered systems:

1. Refer to the Fulton mechanical/electrical drawings during assembly.

2. Ensure that equipment orientation allows for operation interface and

maintenance.

3. Align the skids as shown on the drawings ensuring that skid fasteners (skid

joint angles) are matched. The skid joint angles are a matched set and the
edges of the fasteners should be exactly aligned.

ã

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

Hot pipework and vessels must be
adequately insulated with material
suited to the temperature and
application to prevent both heat loss
and personnel injury.

Advertising