MAINTENANCE

VMPW-IOM-2012-1001

SECTION 4

4-4

Ð

CAUTION

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

All maintenance procedures should
be completed by trained personnel.
Appropriate training and instructions
are available from the Fulton Service
Department at (315) 298-5121 or your
local Fulton Thermal Representative.

In order to meet warranty conditions,
ensure all appropriate maintenance
activities are performed.

6. Fit the hand hole assembly as follows:

» Place the gasket on the hand hole plate and ensure that it is

seating correctly. Do not use any grease, lubricant, or adhesive.

» Position the plate in the boiler. Set the yoke and tighten the

securing nut suffi

ciently enough to provide a snug fi t. Verify

the position of the plate in the boiler, then make it hand tight
and then snug with wrench about 1/4 turn. Do not compress
excessively. See Figures 5 and 6.

» Refi ll the boiler with fresh water.

FIGURE 5 - CORRECT PRESSURE ON GASKET

FIGURE 6 - OVER-COMPRESSED GASKET