SECTION 4

VMPW-IOM-2012-1001

MAINTENANCE

4-15

Troubleshooting Oil Fired Boilers

Problem

Cause

Remedy

Boiler will not maintain
pressure

Oil Supply

Check oil level in supply tank to be sure it is not
below intake line. Fill tank with oil. Check for
clogged nozzle. Clean or replace.

Oil Nozzle

Check for clogged nozzle; clean or replace.

Oil Valve

Check voltage between oil valve leads at terminal
block to be sure oil valve is getting power.

Oil Pump

Check for clogged strainer or fi lter. Remove and
clean. Check for slipping or broken coupling.
Tighten or replace. Check for frozen pump shaft.
Replace.

Aquastat

If power is on, check across aquastats to verify
power through switch. If bad, replace.