Installation – Fulton Caliber (CAL) Condensing Hydronic Boiler User Manual

Page 10

Advertising
background image

© The Fulton Companies 2014

INSTALLATION

CAL-IOM-2014-0129

SECTION 2

2-4

TABLE 1 - OPERATING REQUIREMENTS (SEE TABLE NOTES ON PAGE 2-5)

Caliber Model Size

300

500

750

850

Input (BTU/Hr)

300,000

500,000

750,000

850,000

Output (BTU/Hr)

283,500

472,500

708,750

803,250

Natural Gas Consumption (ft3/hr)

297

495

743

842

Propane Consumption**(ft3/hr)

120

200

300

340

Gas Supply Pressure Minimum
Maximum

4.0

14

4.0

14

4.0

14

4.0

14

Dry Weight LB
KG

500

630

719

729

227

286

326

331

Operating Weight LB
KG

518

662

757

772

235

300

343

350

Control Voltage (V/Hz/Ph)

120/60/1

Blower Voltage (V/Hz/Ph)

120/60/1

X. Electrical Connection*

120/60/1

Y. Condensate Drain Connection* IN

MM

0.75

.075

0.75

0.75

19

19

19

19

Amp Draw

2.1

3.6

3.6

3.6

I. Gas Connection* IN

MM

.75

1

1.25

1.25

19.0

25.4

31.75

31.75

G. Water Inlet/Outlet Connection* IN

MM

1.25

1.5

2

2

31.75

38.1

50.8

50.8

J. Flue Connection (ID)* IN

MM

4.25

4.25

5.875

5.875

108

108

149

149

H. Air Intake Connection***(OD) IN

MM

4.5

4.5

4.5

4.5

114

114

114

114

A. Boiler Width (including feet)* IN

MM

34.5

34.5

34.5

34.5

876

876

876

876

B. Boiler Height* IN

MM

51.6

51.6

51.6

51.6

1310

1310

1310

1310

C. Boiler Depth (Cabinet)* IN

MM

31.25

44

57.25

57.25

793

1117

1454

1454