Operation, Perform pre-start-up inspection, Fill and purge the system – Fulton Caliber (CAL) Condensing Hydronic Boiler User Manual

Page 36: Sola control program presets, Commission the boiler

Advertising
background image

© The Fulton Companies 2014

OPERATION

CAL-IOM-2013-1001

SECTION 3

3-2

Perform Pre-Start-Up Inspection

Prior to start-up, perform the following:

1. Check around the boiler area for the scent of gas. Be sure to check next to

the fl oor, as some gas is heavier than air and will settle. If you smell gas:

» Do not try to light any appliance.

» Do not touch any electrical switch; do not use any phone in your

building.

» Immediately call your gas supplier from a neighbor’s phone.

2. Ensure the boiler is located with the proper clearances as shown in the

Clearances and Serviceability section of this manual.

3. Ensure that relief valves have been properly piped to fl oor drains.

4. Ensure

fl ue gas from the boiler is properly vented.

5. Ensure the water system has been fl ushed and is free of debris.

6. Ensure combustion air openings are not obstructed in any way and have

adequate capacity.

7. Ensure there are no fl ammable liquids, materials or hazardous fumes

present in the environment.

8. Ensure nothing was damaged or knocked loose during installation and/or

shipment, including main gas train and trim assembly.

Fill and Purge the System

Refer to Installation section of this manual for procedure. Attempting to start
the boiler prior to Fill and Purge may result in dry fi re, which can cause injury or
property damage, and is not covered by warranty.

SOLA Control Program Presets

The SOLA control has been factory-programmed and requires no alteration
of program presets. Only factory-trained personnel should attempt to alter
password protected preset values.

Commission The Boiler

Adhere to the following when commissioning the boiler:

1. Verify with authorized personnel that the gas lines have been purged. Do

not proceed without verifi cation.

2. Familiarize all personnel on all aspects of boiler use, safety, and contents

of this manual. This includes, but is not limited to, the use of the controls,
lighting, and shutdown procedures.

!

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct, and strict
adherence to applicable jurisdictional/
professional codes and regulations.
Failure to follow instructions may result
in a fi re or explosion, causing property
damage, personal injury, or loss of life.

This boiler is equipped with an ignition
device, which automatically lights the
burner. Do not try to light the burner by
hand.

Do not store or use gasoline or other
fl ammable vapors and liquids in the
vicinity of this or any other appliances.

WHAT TO DO IF YOU SMELL GAS • Do not
try to light any appliance. • Do not touch
any electrical switch; do not use any phone
in your building. • Immediately call your
gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions. • If
you cannot reach your gas supplier, call
the fi re department. A qualifi ed installer,
service agency or the gas supplier, must
perform installation and service.